I'm looking to purchase a Jib crane for my work. I've been in talks with a company who gave me the following information. The over turning moment is 60,833 in-Lb and the bolt pullout force is 2150 lbs. Using a recommended safety factor of 4, I should design around a bolt pullout force of 8600 lbf.I'm not sure the compressive strength of my concrete, but can I just assume 2500 psi? I would like to stay away from reinforcing the concrete if possible. I do know my concrete is 6' thick.I've been looking at the 3/4' Red head wedge anchor and the pullout strength at an embedded depth of 4.75' is 10561 lbs,My question is there anything else I should consider when looking for anchors?
![](/uploads/1/2/6/7/126763794/953855894.png)
![Template Template](http://toolmonger.com/wp-content/uploads/2008/01/DM_4BoltTemplate.jpg)
RE: Jib Crane Anchor Bolts (Structural) 11 Jul 13 16:06. You may want to look into using Hilti HSL anchors.
. Drill holes in plywood and use as a locator for anchor bolts. NOTES:. Hand hole covers are attached to pole. RAB drilled (non-tenon) poles come pre-drilled for 2 area lights at 180° Additional fixture mounting holes may be drilled in the field. 4 1/4” Bolt Protection Pre-drilled 3 holes on this side not plugged Pre-drilled, plugs installed.
I've done a few jib bases snd have secured a steel plate with threaded studs because of reinforcing locations.I've included an earlier procedure that I've usedPROCEDURE FOR POST INSTALLING JIB CRANE BASE PLATESLOCATE CENTRE POSITION FOR PROPOSED JIB CRANELOCATE FLOOR SLAB REINFORCING IN BOTH DIRECTIONS USING A REBAR LOCATORPROVIDE CHALKLINES TO SHOW LOCATION OF EXISTING REINFORCING STEEL ON THE SURFACE OF THE FLOOR SLABUSING THE JIB CRANE CENTRE, LOCATE CENTRES FOR HILTI HIT-TZ ANCHORSPOSITION HOLES TO FOR THE NEW ANCHORS TO CLEAR EXISTING REINFORCING. DO NOT CUT REINFORCING STEEL. IF REINFORCING IS ENCOUNTERED, TERMINATE HOLE AND RELOCATE ANCHORAGE CLEAR OF ANY REINFORCING STEELADVISE FIELD ENGINEER IF REQUIRED ANCHORAGE LOCATIONS CANNOT BE FIELD ADJUSTED TO AVOID REINFORCING STEEL AND AWAIT FURTHER INSTRUCTIONSPROVIDE HILTI HIT-TZ ANCHORS TO MATCH JIB CRANE BASE PLATE HOLE LOCATIONS. ANCHORS TO MATCH DIA OF ANCHORAGE BOLTSUSING A CARBIDE BIT, DRILL HOLES IN EXISTING CONCRETE FLOOR AT ANCHOR CENTRE LOCATIONS AS STIPULATED BY ANCHOR SUPPLIERTHOUROUGHLY CLEAN OUT DRILLED HOLES AND BLOW OUT ALL LOOSE ‘DUST’TRANSFER ANCHOR LOCATIONS TO PLYWOOD TEMPLATE FOR SETTING ANCHORSINSTALL 8 HILTI HIT-TZ ANCHORS IN HOLES USING HILTI HY-150 HIT ADHESIVE. ANCHOR EMBEDMENT SHALL BE TO MANUFACTURER'S PRINTED INSTRUCTIONSADHESIVE SHALL CURE IN ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONSREMOVE PLYWOOD TEMPLATEPROOF LOAD HILTI-TZ ANCHORS TO THE MANUFACTURER’S SERVICE LOAD CAPACITYPROVIDE A 1/8” THIN SET STERNSON M-BED GROUT LAYER ON THE EXISTING SLABS OVER THE AREA COVERED BY THE STEEL SUPPLEMENTAL JIB BASE PLATEREMOVE EXCESS GROUT MATERIAL AND LET GROUT HARDENINSTALL JIB CRANE OVER HILTI ANCHORS. INSTALL NUTS AND TIGHTEN TO SECURE JIB CRANEJIB CRANE BEAM SUPPLIED SHALL BE PERMANENTLY MODIFIED TO PROVIDE MAX CRANE SPAN STIPULATEDPRIOR TO BEING ‘PUT INTO SERVICE’ JIB CRANES SHALL BE PROOF LOADED TO TWICE THE STIPULATED SERVICE DESIGN LOAD. TESTING SHALL BE IN THE PRESENCE OF A THE CONSULTANT ENGINEERTHE MAXIMUM STIPULATED SERVICE LOAD CAPACITY SHALL BE PAINTED PERMANENTLY AND PROMINENTLY IN 6” HIGH MIN LETTERING ON THE JIB CRANE BEAM IN A CONTRASTING COLOURUse as a general drift.
Modify to suit.Dik RE: Jib Crane Anchor Bolts (Structural) 11 Jul 13 20:55. You are worrying about the wrong thing. Not saying the anchors are unimportant, but a 6' slab is not adequate for support of a jib crane.Agreed.
What transfers your moment and vertical load to the ground?Also, with just a 6' base material thickness you're not going to get much embedment depth allowed.Download Profis, it's free and will check the anchors for you. Use cracked concrete to be safe, and 2,500 psi is a good assumption.You'll be wanting to remove the slab and place a thicker larger slab with dowels into the (e). I am thinking more like 12' thick, min.Click on Link below for Profis.PS Maybe hokie can size that footing for your assuming 1000 or 1500 psf soil bearing capacity.RE: Jib Crane Anchor Bolts (Nuclear) 14 Jul 13 01:14. OK.So assume he doesn't want to cut out the 6 inch concrete floor and replace it with 12 inch deep slab over a region wide enough to anchor the jib crane.Could he 'back-calculate' how wide a frame he needs to reduce the anchor bolt loads enough so a 6 inch slab would work? That is, he figures out how many anchor bolts (4x, 8x, 12x?) over what area of concrete would allow him to stay below the pull-out stress of a 6 inch nominal slab of 2500 psi concrete? Then, obviously, he'd have to connect that frame to the floor, then the jib crane to the frame.
RE: Jib Crane Anchor Bolts (Mechanical) 14 Jul 13 11:25.